Energy & Risk Reduction Programme Case Study 1

Two award-winning Tier III facilities wanted to further optimise their energy performance. Improvements were recommended in the following areas:

Air management

  • Seal air gaps to reduce bypass (data halls)
  • Reduce flow rate (LV switchrooms)
  • Relocate poorly placed grilles (MDF)
  • Redirect air to IT intake (MDF)

Energy

  • Run all AHUs at a lower fan speed (data halls)
  • Reduce pressure set points (data halls)
  • Replace pressure sensors with ones with a tighter range (data halls)
  • Reduce flow rates in LV switchrooms
  • Allow higher temperature in LV switchrooms (no batteries)
  • Reduce pressure set points (MDF)

Risk

  • Review and improve standard and emergency procedures